Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T13CM01472
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/06/2013 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 05/10/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/20/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 05/30/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Verify that the proposed control package for the two rooftop units provides the capability of automatically adjusting the daily start time of the units in order to bring the spaces to the desired temperature at the beginning of the scheduled occupancy. Reference: Section C403.2.4.3.3, IECC 2012. [Initial comment: Show that each rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and start-up control and, if the control does not require manual changeover from the heating and cooling modes, restricts set point overlap. Reference: Sections C403.2.4.1, C403.2.4.2, C403.2.4.3, C403.2.4.3, C403.2.4.3.1, C403.2.4.3.2, and C403.2.4.3.3, IECC 2012.] |
| 05/30/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Clarify the location of the hand sink for room 104; the revised waste and vent diagram shows the hand sink located back-to-back with the hand sink for room 105 but the architectural background and the water supply floor plan show the hand sink located at the west wall of room 104. Coordinate the architectural and plumbing plans. Reference: Section 107.2.1, IBC 2012. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/06/2013 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 06/06/2013 | CPIERCE1 | REJECT SHELF | Completed |