The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T13CM01437
Parcel: 14028008D

Address:
2085 E GANLEY RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T13CM01437
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/21/2013 DAVID RIVERA ZONING REVIEW Denied DSD TRANSMITTAL

FROM: David Rivera
Principal Planner

PROJECT: T13CM01437
Debris Barricade & Fence Crossing at Drainage Channels
Construction Plans

TRANSMITTAL DATE: March 21, 2013

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Zoning has reviewed the plans but cannot approve them at this time. The Development package is still under review and has not been approved.

2. Zoning has reviewed the plans for compliance with the Development Package. The plans submitted for the construction of the crossing do not match what is designed on the development package drawings. It is suggested that the consultants confer with each other and ensure that the final design that is to be used is drawn on both sets of drawings, and should match.

3. Zoning will review the plans on the next submittal to ensure that the development package completed and approved and also to ensure that the crossing plans match the crossing plans on the approved DP.

If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised plan
04/09/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET S1 (FOUNDATION PLANS); STRUCTURAL CALCULATIONS (PAGE 19): THE CALCULATIONS INDICATE A FOOTING AT THE CENTER POST (F1) TO BE 11.5' X 5.25' X 24". THE PLANS INDICATE F1 IS 11'-6" X 4'-9" X 2'-0". CLARIFY.
2. SHEET S1 (NORTH FOUNDATION PLAN); STRUCTURAL CALCULATIONS (PAGE 22): THE CALCULATIONS INDICATE FOOTINGS AT THE END POSTS (F2 OR F3) OF 11.5' X 3.0' X 20". THE PLAN INDICATES F2 IS 10'-6" X 4'-0" X 2'-0", AND F3 IS 8'-0" X 3'-0" X 1'-3". CLARIFY.
3. SHEET S1 (ELEVATION 2); STRUCTURAL CALCULATIONS (PAGE 5): THE CALCULATIONS INDICATE TO DESIGN THE FENCE AND RACK COMPONENTS FOR A MAXIMUM 15'-6" COLUMN SPACING, WHILE THE ELEVATION INDICATES A LARGER SPACING AT THE FENCE ENDS. CLARIFY.
4. SHEET S2 (SECTION 1); STRUCTURAL CALCULATIONS (PAGE 9): THE CALCULATIONS INDICATE A MAXIMUM 9" SPACING OF THE TRASH RACK BRACE BARS. WHERE IS THIS SPACING CALLED OUT ON LTHE DRAWINGS?
5. SHEET S2 (SECTION 1); STRUCTURAL CALCULATIONS (PAGE 25): THE CALCULATIONS INDICATE THE TRASH RACK PLATE ANCHORAGE REQUIRES 4-5/8" DIAMETER ANCHORS WITH 6" EMBEDMENT. IS THIS FOR THE POST BRACE? CLARIFY. ADD CALCULATIONS FOR THE TRASH RACK BASE PLATE AND ANCHORS.
6. SHEET S2; SECTION 1: AT THE CONCRETE CUT OFF WALL, INDICATE THE VERTICAL BARS (#4 @ 12") OCCUR AT EACH FACE.
7. STRUCTURAL CALCULATIONS: PROVIDE CALCULATIONS FOR THE GRADING SUPPORT CONNECTION TO THE CONCRETE CHANNEL (SECTIONS 2A AND 2B ON SHEET S2).
8. GENERAL: PROVIDE A COPY OF THE GEOTECHNICAL EVALUATION REPORT FOR REVIEW.
9. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. NO SUBSEQUENT REVIEWS WILL BE PERFORMED UNTIL THOSE RESPONSES ARE RECEIVED.
04/10/2013 LAITH ALSHAMI ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/29/2013 CPIERCE1 OUT TO CUSTOMER Completed