Permit Number: T13CM01424
Parcel: 137055330

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13CM01424
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/19/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved T13CM01424

As per City of Tucson Commercial Submittal Requirements, provide the following:

On plan assign a circuit number to all circuits, including second lighting sheet .
Provide a location for the panel being used to provide power to new and reused circuits.
Provide updated panel schedules showing updated loads.
Ray Majuta
Elect Plan Review
DSD, City of Tucson
4/19/2013
Ray.Majuta@tucsonaz.gov
04/19/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved