Permit Number: T13CM01424
Parcel: 137055330

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM01424
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/22/2013 CPIERCE1 BUILDING-COMMERCIAL REVIEW Needs Review
03/22/2013 ROBERT SHERRY WATER REVIEW Approved
03/22/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
03/22/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1. PROVIDE CIRCUIT NUMBERS FOR FIXTURES AND RECEPTICLES. ID PANEL THEY WILL FEED FROM, PROVIDE ON PLAN LOCATION OF PANEL & PANEL SCHEDULE SHOWING NEW LOADS.
2. PROVIDE 2012 IECC LIGHTING BUDGET CALCULATION
3. INDICATE HOW LIGHTING IS TO BE SWITCHED OR WHICH CONTACTOR USED.
RAY T MAJUTA
ELECT PLAN REIVEW
PDSD, CITY OF TUCSON
3-19-13
RAY.MAJUTA@TUCSONAZ.GOV
03/22/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed