04/11/2013 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 4-12-13
Activity: T12CM01408
Address: 1360 W. St.Mary's
Applicant: Gabriel Vargas

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code with local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. The City of Tucson has adopted the 2012 International family of codes. As of 1/01/2013 all code references should refer to the currently adopted code or appeal must be made to the Building Official for alternate code use.

PLUMBING PLAN:
2. Provide a gas line isometric and size the supply pipe for the connected demand. Include the length of line and BTU demand for each appliance, size of each branch, total demand, and total developed length from meter to the most remote appliance on the system, G2413.1, Table G2413.4 (1).

ELECTRICAL PLAN:
3. Provide carbon monoxide alarms per R315.
4. Show locations of smoke detectors (every sleeping room and hallways leading to). All smoke detectors must be interconnected with a power source from the building wiring, and shall be equipped with battery backup. When ceiling finish materials are not removed, existing bedrooms may be equipped with battery operated smoke detectors, R314.
5. Show receptacle outlets at each kitchen counter space wider than 12" so that no point along the wall line is more than 24" from a receptacle outlet, E3901.4.1.
6. All outlets shall be protected with combination-type arc-fault breakers (receptacles, lights, and smoke detectors), E3902.12.
7. Bathrooms require a 20-amp circuit with receptacles within 3' of the basin, E3703.4, E3901.6.
8. Water heater may not share the bathroom GFCI circuit.
9. Correct all mislabeled code references.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review