Permit Number: T13CM01403
Parcel: 11005014C

Address:
2930 N SWAN RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM01403
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/12/2013 TERRY STEVENS ZONING REVIEW Approved
03/12/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/12/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
03/12/2013 ROBERT SHERRY WATER REVIEW Approved
03/12/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/12/2013 LAITH ALSHAMI ENGINEERING REVIEW Approved
03/12/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The pipe size called out for common supply to the two urinal flush valves will result in water velocities greater than 8 FPS. Limit the water velocity to less than 8 FPS for the copper piping. Reference: Table 604.3, IPC 2012.
03/12/2013 KEN BROUILLETTE FIRE REVIEW Approved
03/12/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/14/2013 FRODRIG2 WWM REVIEW Needs Review