Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM01403
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/12/2013 | TERRY STEVENS | ZONING | REVIEW | Approved | |
03/12/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
03/12/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
03/12/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
03/12/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
03/12/2013 | LAITH ALSHAMI | ENGINEERING | REVIEW | Approved | |
03/12/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The pipe size called out for common supply to the two urinal flush valves will result in water velocities greater than 8 FPS. Limit the water velocity to less than 8 FPS for the copper piping. Reference: Table 604.3, IPC 2012. |
03/12/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
03/12/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
03/14/2013 | FRODRIG2 | WWM | REVIEW | Needs Review |