Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/11/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T13CM01366 Fire Pump Addition 1. Installation to comply with 2011 NEC rather than 2005,correct electrical specifications. 2. Describe the entry and termination of the fire pump conductors into the existing SES: a. which section will be entered b. are terminations to be onto a busbar and is the busbar predrilled c. describe the room allowed for the new conductors d. what type of lugs are to be used and how connected to bus e. Provide a specification sheet for the Fire Pump Controller f. Describe the type of overcurrent device and setting to be used per 695.4 g. Describe the feeder protection per 695.6 for fire pump conductors. Ray T Majuta Elect Plan Review 3/11/2013 Ray.Majuta@tucsonaz.gov |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/21/2013 | CPIERCE1 | OUT TO CUSTOMER | Completed |