Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T13CM01366
Parcel: 11516036A

Address:
955 W GRANT RD

Review Status: Completed

Review Details: OTHER

Permit Number - T13CM01366
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/11/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM01366
Fire Pump Addition

1. Installation to comply with 2011 NEC rather than 2005,correct electrical specifications.
2. Describe the entry and termination of the fire pump conductors into the existing SES:
a. which section will be entered
b. are terminations to be onto a busbar and is the busbar predrilled
c. describe the room allowed for the new conductors
d. what type of lugs are to be used and how connected to bus
e. Provide a specification sheet for the Fire Pump Controller
f. Describe the type of overcurrent device and setting to be used per 695.4
g. Describe the feeder protection per 695.6 for fire pump conductors.



Ray T Majuta
Elect Plan Review
3/11/2013
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
03/21/2013 CPIERCE1 OUT TO CUSTOMER Completed