Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T13CM01365
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM01365
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/11/2013 TERRY STEVENS ZONING REVIEW Approved
03/11/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
03/11/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Provide up-dated panel schedule for Panel DD.
Ray T Majuta
3/11/2013
03/11/2013 ROBERT SHERRY WATER REVIEW Approved
03/11/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/11/2013 JASON GREEN ENGINEERING REVIEW Approved
03/11/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the design of the mop sink drain so that the vent rises vertically to at least 6" above the flood rim of the mop sink prior to running horizontally. Reference: Section 905.4, IPC 2012.
03/11/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/12/2013 KEN BROUILLETTE FIRE REVIEW Approved
03/22/2013 GERRY KOZIOL WWM REVIEW Approved