Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM01365
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/11/2013 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 03/11/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 03/11/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Provide up-dated panel schedule for Panel DD. Ray T Majuta 3/11/2013 |
| 03/11/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/11/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/11/2013 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 03/11/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Revise the design of the mop sink drain so that the vent rises vertically to at least 6" above the flood rim of the mop sink prior to running horizontally. Reference: Section 905.4, IPC 2012. |
| 03/11/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/12/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 03/22/2013 | GERRY KOZIOL | WWM | REVIEW | Approved |