Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T13CM01360
Parcel: 13355231A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13CM01360
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/19/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The manufacturer's listing of the specified mixing valve does not allow the valve to be located at the water heater: "When used in an ASSE 1017 application at the hot water source, the Watts Thermostatic Mixing Valve Series LFMMV cannot be used by itself to control final temperature at fixtures where ASSE Standard 1016 or ASSE Standard 1070 listed devices are required". Reference: Section 303.2, IPC 2012. [Previous comment: Comment not addressed. Provide temperature mixing valves conforming to ASSE 1070 for the sinks used for hand washing (i.e. BS and HLAV). Reference: Section 416.5, IPC 2012.]

Final Status

Task End Date Reviewer's Name Type of Review Description
04/29/2013 CPIERCE1 APPROVAL SHELF Completed
04/29/2013 CPIERCE1 REJECT SHELF Completed