Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM01340
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/24/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
04/24/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. A design is required for the water heater shelf. Reference: Section 107.2.1, IBC 2012. [Initial comment: Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Section 301.2, IPC 2012.] 2. The Leonard model 170 mixing valve is listed as complying with ASSE 1070; add a note specifying the use of this valve to the drawing. [Initial comment: Clarify that the specified thermostatic mixing valves or faucets for the lavatories shall conform to ASSE 1070. Reference: Section 416.5, IPC 2012.] 3. The water calculations shown on sheet P1.01 show how the water demand was determined; show how the pipe sizes were determined. [Initial comment: Provide water pressure and water pipe sizing calculations. Note that the specified water closet requires a minimum flow pressure of 35 PSI. Reference: Sections 604.1 and 604.3, IPC 2012.] |
04/24/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
04/24/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved |