Review Date Reviewer's Name Type of Review Description Status Comments
04/24/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
04/24/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. A design is required for the water heater shelf. Reference: Section 107.2.1, IBC 2012. [Initial comment: Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Section 301.2, IPC 2012.]
2. The Leonard model 170 mixing valve is listed as complying with ASSE 1070; add a note specifying the use of this valve to the drawing. [Initial comment: Clarify that the specified thermostatic mixing valves or faucets for the lavatories shall conform to ASSE 1070. Reference: Section 416.5, IPC 2012.]
3. The water calculations shown on sheet P1.01 show how the water demand was determined; show how the pipe sizes were determined. [Initial comment: Provide water pressure and water pipe sizing calculations. Note that the specified water closet requires a minimum flow pressure of 35 PSI. Reference: Sections 604.1 and 604.3, IPC 2012.]
04/24/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
04/24/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved