Permit Number: T13CM01336
Parcel: 135057090

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM01336
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/08/2013 STEVE SHIELDS ZONING REVIEW Approved
03/08/2013 LAITH ALSHAMI ENGINEERING REVIEW Approved
03/11/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied New circuits on sheet E1.0 shows a total load of 35.7 amps(four new circuits),provide a panel schedule for Panel DD showing existing and new loads.

Ray T Majuta
Elect Plan Review
3/11/2013
03/11/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
03/11/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/11/2013 ROBERT SHERRY WATER REVIEW Approved
03/11/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the design of the mop sink drain so that the vent rises vertically to at least 6" above the flood rim of the mop sink prior to running horizontally. Reference: Section 905.4, IPC 2012.
03/11/2013 KEN BROUILLETTE FIRE REVIEW Approved
03/11/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/22/2013 GERRY KOZIOL WWM REVIEW Completed