Review Details: COMMERCIAL - TI
Permit Number - T13CM01335
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/08/2013 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 03/08/2013 | LAITH ALSHAMI | ENGINEERING | REVIEW | Approved | |
| 03/11/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Provide updated panel schedule showing new loads. Ray T Majuta 3/11/2013 |
| 03/11/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 03/11/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/11/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/11/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Revise the design of the mop sink drain so that the vent rises vertically to at least 6" above the flood rim of the mop sink prior to running horizontally. Reference: Section 905.4, IPC 2012. |
| 03/11/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 03/11/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/22/2013 | GERRY KOZIOL | WWM | REVIEW | Approved |