Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T13CM01330
Parcel: 10701040B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM01330
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/08/2013 MICHAEL ST. PAUL ZONING REVIEW Approved
03/08/2013 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Approved
03/08/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
03/08/2013 LHANLY1 WATER REVIEW Passed
03/08/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/08/2013 LHANLY1 WWM REVIEW Passed
03/08/2013 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Passed
03/08/2013 JASON GREEN ENGINEERING REVIEW Approved
03/08/2013 MARTIN BROWN FIRE REVIEW Approved
03/08/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed