Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T13CM01280
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/21/2013 | TERRY STEVENS | ZONING | REVIEW | Denied | P&DS TRANSMITTAL FROM: Terry Stevens - Lead Planner PROJECT: T13CM01280 3012 E. Edison St. Addition bathroom / carport / storage room TRANSMITTAL: March 21, 2013 COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1). This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6, .9 & .10. The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A). The proposed addition of a carport with a wall height of 9'-0" along the west property line requires a setback of six (6) feet zero (0) inches. The owner proposes a setback of four (4) feet zero (0) inches. The proposed addition of a bathroom / storage with a wall height of 10'-0" along the east property line requires a setback of six (6) feet eight (8) inches. The owner proposes a setback of four (4) feet zero (0) inches. DDO required. |
| 03/21/2013 | TERRY STEVENS | NPPO | REVIEW | Passed | |
| 05/07/2013 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 05/07/2013 | FRODRIG2 | BUILDING-RESIDENTIAL | REVIEW | Needs Review |