Permit Number: T13CM01265
Parcel: 117067140

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T13CM01265
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/16/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
10/17/2013 MARTIN BROWN FIRE REVIEW Approved
10/28/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The piping materials specified for underground water service use within five-feet of the building (Type K copper) and for the water distribution within the building (Type L copper) will have water velocities in excess of 8.0 FPS with a flow rate of 120 GPM. Verify that the projected water demand will not result in water velocities greater than that recommended by the pipe manufacturer (e.g. limit the water velocity to less than 8 FPS for copper, PEX, or CPVC piping) or revise the pipe sizes. Reference: Table 604.3, IPC 2012.
11/08/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/18/2013 SHANAE POWELL OUT TO CUSTOMER Completed
11/18/2013 CPIERCE1 REJECT SHELF Completed