Permit Number: T13CM01265
Parcel: 117067140

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13CM01265
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/23/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
06/05/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/11/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM01265
335 E Congress

1. Sheet E 4.0, the conductors from the utility transformer to the new SES Retail are listed as "New 4" C each
with 4#3's kcmil AL" for the new 1200 amp SES, insufficient, please correct with proper size and number of runs.
2. Sheet E 4.1, where is the Master Ground Bar to be
located ?

Ray Majuta
Elect Plan Review
PDSD, Tucson
6/12/2013
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
07/02/2013 FERNE RODRIGUEZ OUT TO CUSTOMER Completed
07/02/2013 CPIERCE1 REJECT SHELF Completed