03/12/2013 JASON GREEN ENGINEERING REVIEW Approved
03/15/2013 KEN BROUILLETTE FIRE REVIEW Approved
03/15/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied STRUCTRURAL CALCULATIONS
SHEET B1
1. No beam sizes shown for lower left hand corner of building and 1 above.
a. Drawings, Sheet S201, call for (3) 600S-54. Is this correct?
2. Where calcs call for (B5A 362s 200-54, the drawings show 600s 200-54.
a. Calcs sheet B25 calls for 600S 200-54
c. Please clarify.
SHEET E2
3. Column1 is called for as a TS 7x7x5/16 and drawings call for a 6x6x1/4. Please clarify.
END OF REVIEW
03/15/2013 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/19/2013 STEVE SHIELDS ZONING REVIEW Approved
03/22/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM01265
1. Sheet E4.0, clarify the feeders for the reworked SES from the utility transformer to the SES, the 2011 NEC- 310.15(B)16 does not list 650 kcmil conductors.
2. The Reworked SES going from 400 amp to 1200 amp SES
indicates "new #3/0 CW bond and new # 4 ufer to existing Garage SES. Provide a ground system detail and show if you mean connect to existing ufer ?
3.Sheet E4.0, Electrical One Line Diagram-Alternate #E1, this appears to be the new SES "Retail" as shown on E1.0 Key Note 5, due to there being no connection to existing panels HP1,HL1 and Elevator. However the switchgear is labeled "Replace existing". Since there are indications that this SES is to supply Future Tennants, one line diagrans are confusing. Label SES's as Garage,Residential and Tennants for clarification.
4. Show a new grounding detail for the Retail SES.

Ray Majuta
Elect Plan Review
DSD, Tucson
3/25/2013
Ray.Majuta@tucsonaz.gov
04/01/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The International Plumbing Code, 2012, is the controlling code for this structure, not the 2006 International Plumbing Code. Reference: Section 101, IBC 2012.
2. An approved 2-way cleanout fitting is allowed to be used at the junction of a building drain and a building sewer; otherwise, cleanouts shall open to allow cleaning in the direction of flow. Reference: Sections 708.3.5 and 708.5, IPC 2012.
3. Clarify the invert of the new floor cleanout located near EE.5 - E5.5; it is labeled as both 5.25' BFF and 2.50' BFF on sheet P2.1.
04/01/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
04/01/2013 ROBERT SHERRY WATER REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/20/2013 FERNE RODRIGUEZ OUT TO CUSTOMER Completed