Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T13CM01247
Parcel: 137055270

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM01247
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/05/2013 MICHAEL ST. PAUL ZONING REVIEW Approved
03/12/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Verify that the HVAC unit controls have been provided with an automatic start capability. Reference: Section C403.2.4.3.3, IECC 2012.
2. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restroom will be exhausted with no more than 10% exhausted air being recirculated. Reference: Section 403.2.1 (4), IMC 2012
03/12/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Mechanical Plans Examiner requesting sequence of exfan in restroom to comply with supplied and exhausted air per IMC, show how this will be accomplished electrically.
Ray T Majuta
Elect Plann Review
3/12/2013
03/12/2013 ROBERT SHERRY WATER REVIEW Approved
03/12/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/12/2013 JASON GREEN ENGINEERING REVIEW Approved
03/12/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
03/12/2013 KEN BROUILLETTE FIRE REVIEW Approved
03/12/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/12/2013 ERIC NEWCOMB ADA REVIEW Passed
03/15/2013 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/15/2013 SHANAE POWELL OUT TO CUSTOMER Completed