Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM01247
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/05/2013 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
03/12/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Verify that the HVAC unit controls have been provided with an automatic start capability. Reference: Section C403.2.4.3.3, IECC 2012. 2. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restroom will be exhausted with no more than 10% exhausted air being recirculated. Reference: Section 403.2.1 (4), IMC 2012 |
03/12/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Mechanical Plans Examiner requesting sequence of exfan in restroom to comply with supplied and exhausted air per IMC, show how this will be accomplished electrically. Ray T Majuta Elect Plann Review 3/12/2013 |
03/12/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
03/12/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
03/12/2013 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
03/12/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
03/12/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
03/12/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
03/12/2013 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
03/15/2013 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/15/2013 | SHANAE POWELL | OUT TO CUSTOMER | Completed |