Permit Number: T13CM01164
Parcel: 10408090D

Review Status: Completed

Review Details: REVISION - - 4TH

Permit Number - T13CM01164
Review Name: REVISION - - 4TH
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/20/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/21/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Appliances (e.g. coffee makers) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2012.
2. Waste receptors (i.e. the floor sink) shall not be installed in a cabinet that does not provide ready access to the receptor. Reference: Sections 202 (ready access) and 802.3, IPC 2012.
08/21/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide exhaust for room 38 to accommodate the heat and moisture produced by the coffee maker. Reference: Section 507.2.2, IMC 2012.
08/21/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
09/04/2014 CPIERCE1 APPROVAL SHELF Completed
09/04/2014 CPIERCE1 OUT TO CUSTOMER Completed