Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 4TH
Permit Number - T13CM01164
Review Name: REVISION - - 4TH
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/20/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/21/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Appliances (e.g. coffee makers) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2012. 2. Waste receptors (i.e. the floor sink) shall not be installed in a cabinet that does not provide ready access to the receptor. Reference: Sections 202 (ready access) and 802.3, IPC 2012. |
| 08/21/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide exhaust for room 38 to accommodate the heat and moisture produced by the coffee maker. Reference: Section 507.2.2, IMC 2012. |
| 08/21/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/04/2014 | CPIERCE1 | APPROVAL SHELF | Completed |
| 09/04/2014 | CPIERCE1 | OUT TO CUSTOMER | Completed |