Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T13CM01142
Parcel: 12405007B

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T13CM01142
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/11/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approv-Cond
04/11/2013 MARTIN BROWN FIRE REVIEW Approved
04/19/2013 ROBERT SHERRY WATER REVIEW Approved
04/22/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the gas piping plan on sheet P-1.1and the gas piping riser diagram on sheet P-1.2 (see the relative locations of RTU-1 and RTU-3). [Original comment: Coordinate the gas piping plan on sheet P-1.1and the gas piping riser diagram on sheet P-1.2. Verify the total developed pipe lengths; based on the piping plan, the developed pipe length from the gas meter to RTU-3 is just over 152 feet. Using your pipe sizes, the pressure drop from the meter to RTU-3 exceeds 0.5" of water. Reference: Section 107.2.1, IBC 2012 and Section 402.3, IFGC 2012.]
2. Table 604.3, IPC 2012 indicates that a flush valve for a water closet is to have a minimum design flow rate of 25 GPM. At 25 GPM, a 1", schedule 40 CPVC pipe will have a water velocity of approximately 9.3 feet per second. [Original comment: Verify that the pipe sizes called out for the flush valves will not result in water velocities greater than that recommended by the pipe manufacturer (e.g. limit the water velocity to less than 8 FPS for CPVC piping). Reference: Table 604.3, IPC 2012.]
04/22/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved Still needs certification of special inspectors
04/22/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The fan schedule calls for the exhaust fans to be switched per sheet E-1.1 which states: "Control fans with restroom lights reference switching diagram 9/E-2.1". Detail 9/E-2.1 confirms the note on sheet E-1.1. [Original comment: Revise the sequence of operation for the restroom exhaust fans so that the supply air is exhausted even when the lights are turned off during the operating hours of the building. Reference: Section 403.2.1 (4), IMC 2006.]
2. The revised ventilation calculations do not indicate that a zone air distribution effectiveness value of 0.8 has been applied. [Original comment: Revise the ventilation calculations to include an air distribution effectiveness value of 0.8 (ceiling supply, ceiling return, warm air greater than 15 degrees Fahrenheit above space temperature). Reference: Section 403.3.1.2, IMC 2012.]