Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T13CM01142
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/11/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approv-Cond | |
| 04/11/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/19/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/22/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Coordinate the gas piping plan on sheet P-1.1and the gas piping riser diagram on sheet P-1.2 (see the relative locations of RTU-1 and RTU-3). [Original comment: Coordinate the gas piping plan on sheet P-1.1and the gas piping riser diagram on sheet P-1.2. Verify the total developed pipe lengths; based on the piping plan, the developed pipe length from the gas meter to RTU-3 is just over 152 feet. Using your pipe sizes, the pressure drop from the meter to RTU-3 exceeds 0.5" of water. Reference: Section 107.2.1, IBC 2012 and Section 402.3, IFGC 2012.] 2. Table 604.3, IPC 2012 indicates that a flush valve for a water closet is to have a minimum design flow rate of 25 GPM. At 25 GPM, a 1", schedule 40 CPVC pipe will have a water velocity of approximately 9.3 feet per second. [Original comment: Verify that the pipe sizes called out for the flush valves will not result in water velocities greater than that recommended by the pipe manufacturer (e.g. limit the water velocity to less than 8 FPS for CPVC piping). Reference: Table 604.3, IPC 2012.] |
| 04/22/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | Still needs certification of special inspectors |
| 04/22/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The fan schedule calls for the exhaust fans to be switched per sheet E-1.1 which states: "Control fans with restroom lights reference switching diagram 9/E-2.1". Detail 9/E-2.1 confirms the note on sheet E-1.1. [Original comment: Revise the sequence of operation for the restroom exhaust fans so that the supply air is exhausted even when the lights are turned off during the operating hours of the building. Reference: Section 403.2.1 (4), IMC 2006.] 2. The revised ventilation calculations do not indicate that a zone air distribution effectiveness value of 0.8 has been applied. [Original comment: Revise the ventilation calculations to include an air distribution effectiveness value of 0.8 (ceiling supply, ceiling return, warm air greater than 15 degrees Fahrenheit above space temperature). Reference: Section 403.3.1.2, IMC 2012.] |