Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T13CM01142
Parcel: 12405007B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM01142
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/05/2013 KEN BROUILLETTE FIRE REVIEW Denied Please update plans to current adopted 2012 IFC
03/12/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEET CS
1. The code list is incorrect. Please provide the current city of Tucson adopted building codes listing; i.e the 2012 IBC series with the 2011 NEC and 2009 ICC A117.1.
2. The minimum actual size (not font description) lettering for all drawings, upper and lower case is 3/32" minimum. Please revise all sheets not meeting this standard and resubmit.
SHEET A-0.1
3. Please reference to the large scale partial floor plan 1/A6.3
SHEET A-0.3
4. Detail 4: Please delete all reference to ADA and 2010 IBC (there is no such IBC issue) and reference the 2012 IBC, Section 1110.1 and ICC A 117.1, 2009 Edition, Section 703.
5. Detail 7 is redundant and meaningless, reference sheet 6.3. Please delete this partial floor plan.
SHEET S-0.1
6. Please provide certification of special inspectors as listed in the Special Inspections paragraph.
7. Provide structural calculations for all foundation modification, roof framing modification and for all new and or replaced roof top mounted HVAC equipment.
END OF REVIEW
03/19/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM01142

1. Provide a 2012 IECC Lighting Budget Calculation as required per C of Tuc Submittal Requirements, ComCheck is accepted.
2. Circuits C- 19,21 used on Sheet power circuits, marked spares on panel schedule.

Ray T Majuta
Elect Plan Review
PDSD, C of Tuc.,
3/20/2013
Ray.Majuta@tucsonaz.gov
03/20/2013 ROBERT SHERRY WATER REVIEW Denied Show the location and size of the reduced pressure principle backflow preventer for the water service. Reference: Section 107.2.1, IBC 2012.
03/20/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide reference copies of the civil drawings noted on sheets P-1.1 and P-1.2. Reference: Section 107.2.1, IBC 2012.
2. Coordinate the gas piping plan on sheet P-1.1and the gas piping riser diagram on sheet P-1.2. Verify the total developed pipe lengths; based on the piping plan, the developed pipe length from the gas meter to RTU-3 is just over 152 feet. Using your pipe sizes, the pressure drop from the meter to RTU-3 exceeds 0.5" of water. Reference: Section 107.2.1, IBC 2012 and Section 402.3, IFGC 2012.
3. Verify that the pipe sizes called out for the flush valves will not result in water velocities greater than that recommended by the pipe manufacturer (e.g. limit the water velocity to less than 8 FPS for CPVC piping). Reference: Table 604.3, IPC 2012.
4. Revise detail 3/P-1.1 so that the installation of the wall drain box detail (3/P1.1) complies with the ready access requirement of Section 802.3, IPC 2012. Reference: Section 202, "Ready Access", IPC 2012.
5. Provide protection of the trap seals for all floor drains subject to infrequent use. Reference: Section 1002.4, IPC 2012.
03/20/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the sequence of operation for the restroom exhaust fans so that the supply air is exhausted even when the lights are turned off during the operating hours of the building. Reference: Section 403.2.1 (4), IMC 2006.
2. The occupant load (e.g. on the retail sales floor) used for calculating the minimum required ventilation is to be based on Table 403.3, IMC 2012 or an approved engineering analysis of the specific occupancy type. Reference: Section 403.3, IMC 2012.
3. Revise the ventilation calculations to include an air distribution effectiveness value of 0.8 (ceiling supply, ceiling return, warm air greater than 15 degrees Fahrenheit above space temperature). Reference: Section 403.3.1.2, IMC 2012.
4. Coordinate Specification Section 15940 with the packaged rooftop unit schedule (remark #7) to provide smoke detectors in the return air ducts (or within the RTU), upstream of any filters or outside air connections. Reference: Section 606.2.1, IMC 2012.
5. Show that each rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and start-up control and, if the control does not require manual changeover from the heating and cooling modes, restricts set point overlap. Reference: Sections C403.2.4.1, C403.2.4.2, C403.2.4.3, C403.2.4.3, C403.2.4.3.1, C403.2.4.3.2, and C403.2.4.3.3, IECC 2012.
6. Clarify how the excess air will be relieved during economizer operation. Reference: Section C403.3.1, IECC 2012.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/10/2013 CPIERCE1 REJECT SHELF Completed