Permit Number: T13CM01141
Parcel: 12112402A

Address:
5360 E PIMA ST

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T13CM01141
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/05/2013 JASON GREEN ENGINEERING REVIEW Reqs Change DATE: March 5, 2013
REVIEWER: Jason Green, CFM
ACTIVITY: T13CM01141 (Building Plan)

SUMMARY: Engineering Division of Planning & Development Services Department has received and reviewed the building plan for the solar photovoltaic system with associated parking shade structure. Engineering Division does not recommend approval of the building plan at this time. This review falls under the Unified Development Code (UDC), Administration Manual (AM) and Technical Standards Manual (TSM). Refer to the links for further clarification:
http://cms3.tucsonaz.gov/files/planning/UDC_ADOPTED_100912.pdf; http://cms3.tucsonaz.gov/files/planning/Technical_Manual_ADOPTED_100912.pdf; http://cms3.tucsonaz.gov/files/planning/Admin_Manual_ADOPTED_100912.pdf

BUILDING PLAN COMMENTS:

1) Engineering could not verify that the building plan was in compliance with a stamped approved Development Plan Package. Please submit a Development Plan Package and application for the new proposed structures with associated PV system with the next building plan submittal.

2) Engineering will re-review the building plan on the next submittal to insure compliance with an approved and stamped Development Plan Package. Additional comments may be forthcoming.

3) AM Sec.2-06.3.5: Revise the development plan document to include the approval stamp in the lower right quadrant of each sheet. The link to the stamp can be found here:
http://cms3.tucsonaz.gov/pdsd/cdrc-rezoning/cdrd-stamp

4) AM Sec.2-06.4.3: The relevant Development Plan Package case number (DP13-XXXX) may be added to the lower right hand corner of the plan on all sheets.

5) AM Sec.2-06.4.9.H.5: Verify the development plan document is designed in accordance with Sec.7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC.


GENERAL COMMENTS:

Please provide a Development Plan Package and building plan at resubmittal. Further comments may be generated upon resubmittal of the plan review.

For questions or to schedule an appointment I can be reached at 837-4929.




Jason Green, CFM
Senior Engineer Associate
Engineering Division
Planning & Development Services
03/06/2013 KEN BROUILLETTE FIRE REVIEW Approved This is a U occupancy and is not subject to 605.11 of the 2012 IFC
03/13/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET I-10; BUILDING CODES: THE IBC, IFC, IECC, IMC, AND IPC APPROVED EDITIONS ARE 2012. REVISE THE NOTES.
2. SHEET S-1.2; GENERAL NOTES: THERE ARE SEVERAL LOCATIONS WHERE THE 2006 IBC IS REFERENCED. REVISE THE NOTES AND ENSURE THAT DESIGNS MEET THE 2012 IBC REQUIREMENTS.
3. STRUCTURAL CALCULATIONS; SHEET 1: THE BUILDING CODE INDICATED IN THE CALCULATIONS IS THE 2006 IBC. REVISE THE REFERENCE BUILDING CODE, AND VERIFY THE DESIGN MEETS THE 2012 IBC REQUIREMENTS. THERE IS A CITY OF TUCSON AMENDMENT TO THE IBC, ADDING A SECTION 1609.5.1.1 CONCERNING WIND UPLIFT RESISTANCE TO MINIMIZE MICROBURST EFFECTS. VERIFY AND INDICATE IN THE CALCULATIONS METHOD 1 OR METHOD 2 UPLIFT REQUIREMENTS ARE MET, AND INCLUDE THE CALCULATIONS.
4. STRUCTURAL CALCULATIONS; SHEET 20: VERIFY THE FOUNDATION INDICATED WILL RESIST THE DESIGN UPLIFTS CALCULATED PER THE CITY OF TUCSON AMENDMENT (SECTION 1609.5.1.1) TO THE 2012 IBC.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. SUBSEQUENT REVIEWS WILL NOT BE PERFORMED WITHOUT RESPONSES.
03/15/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
03/19/2013 TERRY STEVENS ZONING REVIEW Denied Zoning cannot approve this plan until a development package has been submitted and approved. This review can be done over the counter once the DP has been approved.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/03/2013 SHANAE POWELL OUT TO CUSTOMER Completed
04/03/2013 CPIERCE1 REJECT SHELF Completed