Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM01106
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/09/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/09/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 04/11/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Verify the existing connected gas load and its associated developed pipe length; the submitted information indicates the existing gas piping is too small to accommodate the connected gas load. [Initial comment: Provide gas pipe sizing calculations demonstrating conformance to Section 402.1 and 402.3, IFGC 2012.] |
| 04/11/2013 | ROBERT SHERRY | WATER | REVIEW | Denied | 1. The comment is directed at the existing water meter serving the building, located near the property line and not a meter located within the building. [Initial comment: Provide the size of the water meter and its total connected demand.] 2. See comment 1.[Initial comment: Provide location and size of the reduced pressure principle backflow protector associated with the water meter.] |