Permit Number: T13CM01106
Parcel: 13734001E

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM01106
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/09/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/11/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Verify the existing connected gas load and its associated developed pipe length; the submitted information indicates the existing gas piping is too small to accommodate the connected gas load. [Initial comment: Provide gas pipe sizing calculations demonstrating conformance to Section 402.1 and 402.3, IFGC 2012.]
04/11/2013 ROBERT SHERRY WATER REVIEW Denied 1. The comment is directed at the existing water meter serving the building, located near the property line and not a meter located within the building. [Initial comment: Provide the size of the water meter and its total connected demand.]
2. See comment 1.[Initial comment: Provide location and size of the reduced pressure principle backflow protector associated with the water meter.]