Review Date Reviewer's Name Type of Review Description Status Comments
02/27/2013 RONALD BROWN ADA REVIEW Passed
03/11/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/18/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
03/19/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide the rooftop units AC-1 and AC-2 with a thermostatic control that provides for off-hour and set-back control, automatic shutdown and start-up control and, if the control does not require manual changeover from the heating and cooling modes, restricts set point overlap. Reference: Sections C403.2.4.1, C403.2.4.2, C403.2.4.3, C403.2.4.3, C403.2.4.3.1, C403.2.4.3.2, and C403.2.4.3.3, IECC 2012.
2. Provide economizers for the rooftop units AC-1 and AC-2 along with means for relieving the excess air during economizer operation or increase the efficiency of the rooftop units per Table C403.3.1 (2), IECC 2012. Reference: Section C403.3.1, IECC 2012.
3. Verify that the parapet height within ten feet of exhaust fan EF-1 is at least 42" above the walking surface of the roof or provide guards for the fan per Section 304.11, IMC 2012.
4. Provide guards for AC-1, it appears to be located within 10 feet of a roof edge or of a walking surface that is elevated more than 30 inches above the adjoining grade. Reference: Section 304.11, IMC 2012.
5. Coordinate the sequence of operation for exhaust fan EF-3 with the electrical design. The electrical design shows the fan being controlled by an occupancy sensor. Reference: Section 403.2.1, IMC 2012.
6. Verify that the listed exhaust flow rate for the specified Type I hood (KH-1) is the same as the exhaust flow rate specified in the equipment schedule. Reference: Section 507.1, IMC 2012.
7. Provide structural calculations and details to show that the Type I hood (KH-1) is supported from the building structure in accordance with Section 507.6, IMC 2006. Reference: Section 302.1, IMC 2012.
8. Show that the hood installation complies with Section 507.9, IMC 2012, for clearances (i.e. is the existing furring metal or wood?).
03/19/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Verify that the new 3-compartment sink will be installed with a direct waste connection for the wash and rinse sections and with an indirect connection for the sanitizing compartment. Reference: Section 802.1, IPC 2012.
03/20/2013 MARTIN BROWN FIRE REVIEW Approved