Permit Number: T13CM01082
Parcel: 116126300

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM01082
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/11/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/18/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
03/19/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
03/19/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide the rooftop unit, HP-1, with a thermostatic control that provides for off-hour and set-back control, automatic shutdown and start-up control and, if the control does not require manual changeover from the heating and cooling modes, restricts set point overlap. Reference: Sections C403.2.4.1, C403.2.4.2, C403.2.4.3, C403.2.4.3, C403.2.4.3.1, C403.2.4.3.2, and C403.2.4.3.3, IECC 2012.
2. Provide an economizer for the rooftop unit, HP-1, along with means for relieving the excess air during economizer operation or increase the efficiency of the rooftop unit per Table C403.3.1 (2), IECC 2012. Reference: Section C403.3.1, IECC 2012.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/20/2013 SHANAE POWELL OUT TO CUSTOMER Completed
03/20/2013 CPIERCE1 REJECT SHELF Completed