Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T13CM01007
Parcel: 128100540

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM01007
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/21/2013 DAVID RIVERA ZONING REVIEW Approved
02/21/2013 LAITH ALSHAMI ENGINEERING REVIEW Approved
02/21/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Double doors not accessible as per ICC A117.1, Section 404.2.5.
2. Note "C", incorrect discription of work to be completed, provide new double smoke doors at elevator lobby.
3. Provide all exiting hardware required as per 2012 IBC, Section 1008.1.10.
END OF REVIEW
02/27/2013 SPOWELL1 MECHANICAL-COMMERCIAL REVIEW Needs Review
02/27/2013 SPOWELL1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
02/27/2013 SPOWELL1 WATER REVIEW Needs Review
02/27/2013 MARTIN BROWN FIRE REVIEW Approved
02/27/2013 SPOWELL1 WWM REVIEW Needs Review
02/27/2013 SPOWELL1 PLUMBING-COMMERCIAL REVIEW Needs Review
02/27/2013 SPOWELL1 ADA REVIEW Needs Review
02/27/2013 SHANAE POWELL COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review