Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM01007
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/21/2013 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 02/21/2013 | LAITH ALSHAMI | ENGINEERING | REVIEW | Approved | |
| 02/21/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Double doors not accessible as per ICC A117.1, Section 404.2.5. 2. Note "C", incorrect discription of work to be completed, provide new double smoke doors at elevator lobby. 3. Provide all exiting hardware required as per 2012 IBC, Section 1008.1.10. END OF REVIEW |
| 02/27/2013 | SPOWELL1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 02/27/2013 | SPOWELL1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 02/27/2013 | SPOWELL1 | WATER | REVIEW | Needs Review | |
| 02/27/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 02/27/2013 | SPOWELL1 | WWM | REVIEW | Needs Review | |
| 02/27/2013 | SPOWELL1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 02/27/2013 | SPOWELL1 | ADA | REVIEW | Needs Review | |
| 02/27/2013 | SHANAE POWELL | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |