Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 3RD
Permit Number - T13CM00975
Review Name: REVISION - - 3RD
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/21/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | The new ramp on sheet A1.7 provide for an 8'-0" long run for a height of 1'-2" which calculates to a 14.6% slope. On sheet A3.1, detail 3, the slope is called out as 1.5 to 6 or a 25% slope. Section 1010.3 of the 2012 IBC states that pedestrian ramps not a part of the means of egress can be no steeper than 12.5%. Please reconcile. END OF REVIEW |
10/21/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
10/21/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide sheet M6.09 (referenced by keynote 10 on sheet M3.05). |
10/21/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
10/21/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/06/2013 | CPIERCE1 | REJECT SHELF | Completed |