Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T13CM00975
Parcel: 14041009A

Review Status: Completed

Review Details: REVISION - - 3RD

Permit Number - T13CM00975
Review Name: REVISION - - 3RD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/21/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied The new ramp on sheet A1.7 provide for an 8'-0" long run for a height of 1'-2" which calculates to a 14.6% slope. On sheet A3.1, detail 3, the slope is called out as 1.5 to 6 or a 25% slope. Section 1010.3 of the 2012 IBC states that pedestrian ramps not a part of the means of egress can be no steeper than 12.5%. Please reconcile.
END OF REVIEW
10/21/2013 KEN BROUILLETTE FIRE REVIEW Approved
10/21/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide sheet M6.09 (referenced by keynote 10 on sheet M3.05).
10/21/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/21/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/06/2013 CPIERCE1 REJECT SHELF Completed