Review Date Reviewer's Name Type of Review Description Status Comments
02/21/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/22/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Place the structural details on the drawings. [Original comment: Provide structural details to show how the fan coil units are to be connected to the building structure. Reference: Section 302.1, IMC 2012.]
02/22/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The submitted structural calculation for the water heater support limits the load on the platform to 300 pounds. The specified water heater weighs 350 pounds; reevauate the support platform. [Original comment: Provide information to show how the proposed water heater platform is to be supported from the building structure. Reference: Sections 106.3.1 and 301.2, IPC 2006.]
02/26/2013 CPIERCE1 WWM REVIEW Needs Review