Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM00902
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/21/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/22/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Place the structural details on the drawings. [Original comment: Provide structural details to show how the fan coil units are to be connected to the building structure. Reference: Section 302.1, IMC 2012.] |
| 02/22/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The submitted structural calculation for the water heater support limits the load on the platform to 300 pounds. The specified water heater weighs 350 pounds; reevauate the support platform. [Original comment: Provide information to show how the proposed water heater platform is to be supported from the building structure. Reference: Sections 106.3.1 and 301.2, IPC 2006.] |
| 02/26/2013 | CPIERCE1 | WWM | REVIEW | Needs Review |