Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM00902
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/15/2013 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 02/15/2013 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 02/15/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/15/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A0; SUMMARY OF GOVERNING REGULATIONS: REVISE THE ACCESSIBILITY CODE TO THE 2009 EDITION AND THE FIRE PREVENTION CODE TO THE 2012 EDITION. 2. SHEET A1 (FLOOR PLAN KEYNOTES); SHEET P2 (DETAIL 1): THE WATER HEATER DETAIL INDICATES TO SEE THE ARCHITECTURAL PLANS FOR SUPPORT STRUCTURE ABOVE. THAT INFORMATION IS NOT SHOWN. PROVIDE A DETAIL OF HOW THE ALL THREAD IS SUPPORTED ABOVE, AND GIVE THE SIZE OF THE ROD AND SUPPORT MEMBERS. 3. SHEET A3; DETAIL 8: IT APPEARS PART OF THE BRACING NOTE IS MISSING. PROVIDE. 4. GENERAL: IF A CERTIFICATE OF OCCUPANCY IS REQUIRED, PROVIDE THE OCCUPANT LOAD ON THE DRAWINGS. |
| 02/15/2013 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 02/19/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide structural details to show how the fan coil units are to be connected to the building structure. Reference: Section 302.1, IMC 2012. |
| 02/19/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide information to show how the proposed water heater platformis to be supported from the building structure. Reference: Sections 106.3.1 and 301.2, IPC 2006. |
| 02/19/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/19/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 02/19/2013 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/21/2013 | CPIERCE1 | WWM | REVIEW | Needs Review |