Permit Number: T13CM00793
Parcel: 126062620

Address:
4225 E TEXAS CI

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T13CM00793
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/08/2013 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied T13CM00793
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and the 2012 International Energy Conservation Code. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

FOUNDATION PLANS:

1. Locate and specify all anchor-bolt spacing on the foundation plan. Minimum ½" diameter with (anchor bolt length for assuring) 7" embedment into concrete or masonry, R319.1 & R403.1.6. Maximum spacing 6' o/c and within 12" of each sill plate end, R403.1.6.

SECTIONS - DETAILS:

1. Clarify Detail references notated at Elevation General Notes #D & E/A4.0, R106.1.1.
2. Show the ceiling gypsum board as either 5/8" or ½" sag resistant when applied to 24" o/c ceiling framing, IRC table R702.3.5 footnote d.
3. Show fiber-cement board or glass mat gypsum backers for tiled walls in tub and shower areas, R702.4.2.
4. Provide detail or notation for the bracing of trusses at gable ends to prevent rotation and provide lateral stability, R802.10.3.

PLUMBING PLANS:

1. Tucson Water Department limits 5/8" water meters to a maximum of 11 IRC fixture units or 15 gallons per minute. Specify a ¾" water meter upgrade.
2. Provide the water pipe diameter between the meter and shut off valve in compliance with, P2903.7. A minimum 1" service pipe is required for supplying water to more than 9.5 fixture units.
3. Show gas pipe sizes in compliance with connected demand, G2413.3 & Table G2413.4(1). Provide a 1-1/4" gas line between the meter and first tee.

MECHANICAL PLANS:

1. Provide Manual J/S/D calculations in accordance with M1401.3, M1601.1.
2. Provide return air duct and register sizes meeting minimum requirements of 72 SQ IN/ ton, M1403. Minimum duct/register size: heat pump or air conditioner - 6 SQ IN per 1,000 BTU (1 ton cooling = 12,000 BTU). The 4 ton unit requires a minimum 20" diameter return air duct.

ELECTRICAL PLANS:

1. Notate the requirement for a carbon monoxide detector outside of bedroom doors, R315.
2. Show the location of each outlet on the Electrical Plan, E3305.1. Include circuit #7, 11, 14, 21 & 23.
3. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3603.2 and E3801.3 through E3801.4.5.
4. Show a GFCI receptacle outlet on the same level within 25' of exterior HVAC equipment, E3801.11.
5. Protect all outlets (except required GFCI circuits) including receptacles, lights and smoke detectors with combination type arc-fault circuit interrupters, E3902.12.
6. Protect extended branch circuits with combination type arc-fault circuit interrupters, or an AFCI type receptacle at the first outlet on the branch circuit, E3902.13.

OUTDOOR LIGHTING CODE

1. Show the proposed fixture as full cut-off FCO style, or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing and skylights is U=0.65, ceiling R=38 and walls R=13. Show appropriate "R" values of insulation and the maximum "U" factors of the windows and doors on the plans, N1102.1.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/15/2013 CPIERCE1 OUT TO CUSTOMER Completed