Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/WWM
Permit Number - T13CM00763
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/07/2013 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Denied | T13CM00763 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and the 2012 International Energy Conservation Code. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL REQUIREMENTS: All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration. FOUNDATION PLANS: 1. Show the minimum 12" footing depth below undisturbed soil, R403.1.4. Clarify Detail #6, 8 & 9/S1. STRUCTURAL PLANS: 1. Show a beam size with appropriate load carrying capacity, R301.1. The 4x Carport beams are undersized. SECTIONS - DETAILS: 1. Provide consistent material and size references on plans, notes and details, R106.1.1. Clarify roof sheathing thickness shown on the Framing Plan, GSN for OSB and Details #3 & 4/S1. 2. Show the ceiling gypsum board as either 5/8" or ½" sag resistant when applied to 24" o/c ceiling framing, IRC table R702.3.5 footnote d. 3. Show fiber-cement board or glass mat gypsum backers for tiled walls in tub and shower areas, R702.4.2. PLUMBING PLANS: 1. Show any underground gas piping beneath buildings encased in an approved sealed & vented conduit, G2415.11. 2. Clarify the demands shown on the Gas Pipe Sizing schedule for Outlet ExA and Outlet G. These values are not as shown for the appliance demands. 3. Show gas pipe sizes in compliance with connected demand, G2413.3 & Table G2413.4(1). The maximum demand for a 1" pipe with 140' developed length is 157 CFH. MECHANICAL PLANS: 1. Provide Manual J/S calculations in accordance with M1401.3, M1601.1. 2. Show dryer vent size and location for venting to exterior, M1501. ELECTRICAL PLANS: 1. Protect all outlets (except required GFCI circuits) including receptacles, lights and smoke detectors with combination type arc-fault circuit interrupters, E3902.12. 2. Protect extended branch circuits with combination type arc-fault circuit interrupters, or an AFCI type receptacle at the first outlet on the branch circuit, E3902.13. INTERNATIONAL ENERGY CONSERVATION CODE: 1. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing and skylights is U=0.65, ceiling R=38 and walls R=13. Show overall compliance if using less than prescribed component values by providing a RES check calculation. If you have any questions please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/22/2013 | CPIERCE1 | OUT TO CUSTOMER | Completed |