Permit Number: T13CM00706
Parcel: 133231460

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM00706
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/06/2013 TERRY STEVENS ZONING REVIEW Approved
02/06/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/06/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
02/06/2013 ROBERT SHERRY WATER REVIEW Approved
02/06/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A1; DEMOLITION PLAN KEYNOTES: NOTE 108 WAS NOT LOCATED ON THE PLAN. VERIFY.
2. SHEET A1; FLOOR PLAN KEYNOTES: IN NOTE 5, INDICATE THE METAL STUD SPACING.
3. SHEET A1; FLOOR PLAN NOTES: NOTE 2 REFERENCES SHEET A3 FOR WALL MATERIALS AND FINISHES. REVISE.
4. SHEET A4; DETAIL 15: INDICATE THE SIZE AND QUANTITY OF THE CONNECTORS FOR THE BRACE TO THE TOP OF THE WALL AND TO THE STRUCTURE ABOVE.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
02/06/2013 JASON GREEN ENGINEERING REVIEW Approved
02/06/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/06/2013 KEN BROUILLETTE FIRE REVIEW Denied PLEASE UPDATE DRAWINGS TO 2012 INTERNATIONAL CODES
02/06/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/06/2013 ERIC NEWCOMB ADA REVIEW Passed
02/13/2013 GERRY KOZIOL WWM REVIEW Passed