Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM00706
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/06/2013 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 02/06/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 02/06/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/06/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/06/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A1; DEMOLITION PLAN KEYNOTES: NOTE 108 WAS NOT LOCATED ON THE PLAN. VERIFY. 2. SHEET A1; FLOOR PLAN KEYNOTES: IN NOTE 5, INDICATE THE METAL STUD SPACING. 3. SHEET A1; FLOOR PLAN NOTES: NOTE 2 REFERENCES SHEET A3 FOR WALL MATERIALS AND FINISHES. REVISE. 4. SHEET A4; DETAIL 15: INDICATE THE SIZE AND QUANTITY OF THE CONNECTORS FOR THE BRACE TO THE TOP OF THE WALL AND TO THE STRUCTURE ABOVE. 5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 02/06/2013 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 02/06/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 02/06/2013 | KEN BROUILLETTE | FIRE | REVIEW | Denied | PLEASE UPDATE DRAWINGS TO 2012 INTERNATIONAL CODES |
| 02/06/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/06/2013 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 02/13/2013 | GERRY KOZIOL | WWM | REVIEW | Passed |