Review Date Reviewer's Name Type of Review Description Status Comments
02/08/2013 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied T13CM00693
PLAN REVIEW COMMENTS
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2005 National Electrical Code and Arizona Revised Statutes. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

GENERAL NOTES:
" Limit all code references to those recognized by the City of Tucson. The 2011 NEC and 2012 IRC are listed at the Planning & Development Services web site. Change all code references on each sheet.
" Clarify the number of panels. Sheet #3 shows three arrays of 9 panels. Sheet #5 lists rack A with 15 panels and rack B with 4 panels.
DIAGRAMS / CALCULATIONS
1. Show the sum of the main and backfed breakers does not exceed 120% of the busbar rating, NEC 690.64 (B) (2). Main breaker replacement may not negatively affect the equipment integrity or listing, NEC 110.3. Provide an electrical load calculation if reducing the main protection.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/12/2013 CPIERCE1 REJECT SHELF Completed