Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T13CM00696
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/07/2013 | MARTIN BROWN | FIRE | REVIEW | Denied | Applicable code section on sheet G-100 references 2003 International Fire Code. Plans submitted after January 1st, 2013 must comply to the 2012 edition. The 2012 edition has a whole new section pertaining to solar (section 605.11). Please review this section and verify plans conform to new solar standards, including signage. Edit sheet G-100 to reflect correct standards. |
| 03/01/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T13CM00696 1. Plans must be sealed by a registrant (EE),per Tucson Commercial Submittal Requirements. 2. All plans to be minimum text size 3/32" also upper and lower case, per Commercial Submittal Requirements 3. Installation to comply with 2011 NEC, notate on cover and electrical sheets. 4. Highlight selected models on submitted datasheets. Ray T Majuta Elect Plan Review PDSD, Tucson 3/1/2013 Ray.Majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/08/2014 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 09/08/2014 | CPIERCE1 | REJECT SHELF | Completed |