Permit Number: T13CM00696
Parcel: 12714003N

Address:
445 N WILMOT RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T13CM00696
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/07/2013 MARTIN BROWN FIRE REVIEW Denied Applicable code section on sheet G-100 references 2003 International Fire Code. Plans submitted after January 1st, 2013 must comply to the 2012 edition. The 2012 edition has a whole new section pertaining to solar (section 605.11).
Please review this section and verify plans conform to new solar standards, including signage. Edit sheet G-100 to reflect correct standards.
03/01/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM00696

1. Plans must be sealed by a registrant (EE),per Tucson Commercial Submittal Requirements.
2. All plans to be minimum text size 3/32" also upper and lower case, per Commercial Submittal Requirements
3. Installation to comply with 2011 NEC, notate on cover and electrical sheets.
4. Highlight selected models on submitted datasheets.

Ray T Majuta
Elect Plan Review
PDSD, Tucson
3/1/2013
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
09/08/2014 CPIERCE1 OUT TO CUSTOMER Completed
09/08/2014 CPIERCE1 REJECT SHELF Completed