Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T13CM00695
Parcel: 12709011J

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T13CM00695
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/06/2013 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/07/2013 MARTIN BROWN FIRE REVIEW Denied Applicable code section on sheet G-100 references 2003 International Fire Code. Plans submitted after January 1st, 2013 must comply to the 2012 edition. The 2012 edition has a whole new section pertaining to solar (section 605.11).
Please review this section and verify plans conform to new solar standards, including signage. Edit sheet G-100 to reflect correct standards.
02/08/2013 JASON GREEN ENGINEERING REVIEW Approved February 8, 2013
FLOODPLAIN USE PERMIT NO.: T13OT00160
ADDRESS: 6199 E Broadway Blvd Tucson, Arizona 85711
PROPERTY OWNER: Family Housing Resources
6199 E Broadway Blvd Tucson, Arizona 85711

The applicant is authorized to use a portion of the FEMA Special Flood Hazard Area Zone AH floodplain per the Flood Insurance Rate Maps 04019C2301L, specifically described as:

A portion of Parcel 127-09-011J.
For the purpose of installing a photovoltaic system to an existing non-conforming building

In reviewing this Floodplain Use Permit application for improvements to an existing floodprone structure, it has been concluded that the cumulative value of proposed improvements to this structure, as supported by documentation provided by the applicant, is less than 50% of the current value of the existing structure.

The applicant agrees to comply with City of Tucson Floodplain and Erosion Hazard Area Regulations, and is bound by the conditions stated below. Violation of any of the conditions stated or referred to below, as determined by the City Engineer, shall be grounds for revocation of this permit. Responsibility for renewal of this permit, if necessary, is with the applicant. Issuance of this permit does not constitute a waiver of other requirements contained in the Tucson City Code, UDC, or any other Federal, State, or local regulation. No use other than as permitted herein is allowed. Additional uses allowed under City of Tucson Floodplain and Erosion Hazard Regulations require application for, review and approval of an additional Floodplain Use Permit.

This floodplain use permit is issued with the following 11 conditions:
1) All improvements proposed under this permit will be cumulative in percentage, to include this project.
2) The proposed improvements shall not impose conditions that would increase the flood damage potential to the combined proposed and existing building, by 50 percent or greater of the existing structure's value.
3) A cost estimate was submitted showing that the improvements are less than 50 % (estimate was 4.3%) of the assessed value ($2,497,336) as shown on the Pima County Assessors Website. No person shall repair or alter property in a piecemeal manner so as to avoid the provisions of Section 26-4.1.a.3, Chapter 26-Tucson Code. The estimate will be recorded and if piecemeal permits for this construction are applied for the cost estimate will be added to it.
4) Except as approved by the City Engineer prior to the start of construction, development under this permit shall not obstruct, retard or divert the existing flow of floodwaters from or to adjacent properties.
5) This Floodplain Use Permit is issued concurrently with the improvement plans/permit. Copies of these documents shall be kept in a readily accessible location on site at all times.
6) Any future permanent, freestanding walls or other structures shall have separate floodplain use permit applications submitted to this office for review and approval.
7) An application/processing fee of $50.00 (submittal fee) must accompany each future request for work to be authorized under this floodplain use permit. Engineering study review fees of $150.00 may be imposed based upon the fee schedule in the current floodplain ordinance.
8) The associated improvements are with permit activity number T13CM00695.
9) The applicant attests to the fact that the plans and documents submitted represent all of the improvements that will be done to the existing building, and that all additions, improvements or repairs to the building are included in the construction plans and/or documents herewith. No other improvements, repairs, reconstruction, additions or remodeling have been made to the structure that is not indicated in the attached plans and/or documents.
10) Renewal of this permit will require a new application, review and approval of that application by the City of Tucson Planning & Development Services Department, Engineering Division. This permit may be renewed for up to one year at the sole discretion of the City Engineer or designated representatives.
11) This permit is specific to the improvements for 6199 E Broadway Blvd as indicated on the approved plans. It shall not apply to any other structure or property, whether attached or unattached, not specified under this permit.

This Floodplain Use Permit will be automatically revoked and becomes invalid if conditions are not complied with, as set forth in this permit.

APPLICANT NAME: Cogenca Development
ADDRESS: 365 E Middfield Rd Mountain View, CA 94043
PHONE: 350-230-3430
OWNER: Family Housing Resources
ADDRESS: 6199 E Broadway Blvd Tucson, AZ 85711
PHONE: N/A

(EXPIRATION DATE) Month: 02 Day: 08 Year: 2014

SIGNATURE OF APPLICANT DATE

The applicant is authorized by the City Engineer to receive a floodplain use permit subject to the above referenced conditions and restrictions.
02/28/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM00695

1. Plans must be sealed by a registrant (EE) per Tucson Commercial Submittal Requirements.
2. All text to be minimun 3/32" upper and lower case, per Tucson Commercial Submittal Requirements.
3. Installation to comply with 2011 NEC, notate on cover and electrical sheets.
4. Highlight the models selected on data sheets submitted for PV equipment.

Ray T Majuta
Elect Plan Rewview
PDSD, Tucson,
3/1/2013
Ray.Majuta@tucsonaz.gov
E

Final Status

Task End Date Reviewer's Name Type of Review Description
04/23/2013 FERNE RODRIGUEZ OUT TO CUSTOMER Completed