Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM00621
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/01/2013 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
02/01/2013 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
02/04/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
02/04/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted with no more than 10% exhausted air being recirculated. Reference: Section 403.2.1 (4), IMC 2012. |
02/04/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
02/04/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
02/04/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
02/04/2013 | RONALD BROWN | ADA | REVIEW | Passed | |
02/04/2013 | RONALD BROWN | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
02/05/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
02/07/2013 | FRODRIG2 | WWM | REVIEW | Needs Review |