Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T13CM00620
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/08/2013 | LEERAY HANLY | MECHANICAL-COMMERCIAL | REVIEW | Denied | ORIGINAL CORRECTION REQUEST NOT ADDRESSED: Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted with no more than 10% exhausted air being recirculated. Reference: Section 403.2.1 (4), IMC 2012. |