Permit Number: T13CM00620
Parcel: 12801005H

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13CM00620
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/08/2013 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Denied ORIGINAL CORRECTION REQUEST NOT ADDRESSED:
Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted with no more than 10% exhausted air being recirculated. Reference: Section 403.2.1 (4), IMC 2012.