Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T13CM00607
Parcel: 10309064B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13CM00607
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/05/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
03/18/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved; provide an approved engineering analysis of the specific occupancy of rooms 111 and 122 with supporting statistical data or use the occupant density value for the telephone/data entry areas shown in Table 403.3, IMC 2012. [Original comment: The occupant load used to calculate the required ventilation is not necessarily the same as the occupant load used for calculating exiting requirements. The occupant load used for calculating the minimum required ventilation is to be based on Table 403.3, IMC 2012 (e.g. telephone/data entry has an occupancy rate of 60 people pre 1,000 square feet) or an approved engineering analysis of the specific occupancy type with supporting statistical data. Reference: Section 403.3, IMC 2012.]
03/18/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Verify that the specified trap primer can successfully deliver water to a trap located approximately 70-feet from the distribution unit. [Original comment: Provide protection of the trap seals for floor drain FD-2. Reference: Section 1002.4, IPC 2012.]

Final Status

Task End Date Reviewer's Name Type of Review Description
03/29/2013 SHANAE POWELL OUT TO CUSTOMER Completed
03/29/2013 CPIERCE1 REJECT SHELF Completed