Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T13CM00607
Parcel: 10309064B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM00607
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/07/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM00607
3760 N Commerce Dr #100
TI Office

1.Indicate voltages for all fixtures on Sheet E301.1
2. Sheet E102., show where the existing Junction boxes located that the new 400 amp feeders are to be spliced on to feed MLB and EDPA Switchboards ?
3. Where are MDP and EDP located ?
4. Provide the existing loads on MDP and EDP and include new MLB and EDPA loads for new total. How were existing loads obained ?
5. Provide the fault current leveles at MDP and EDP, provide the fault current levels downstream to new equipment and show how brought down to 10AIC. Show faulf current values for panels in schedules.
6. Provide IECC 2012 Budget Lighting Calculation for new lighting, Com-Check ok.
7. Size grounds for transformers.

Ray T Majuta
Elect Plan Review
PDSD, City of Tucson
2/08/2013
Ray.Majuta@tucsonaz.gov
02/13/2013 MARTIN BROWN FIRE REVIEW Approved
02/14/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
02/15/2013 ROBERT SHERRY WATER REVIEW Approved
02/15/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide tempered water for the lavatories using approved devices conforming to ASSE 1070. Reference: Section 416.5, IPC 2012.
2. Relocate the proposed backflow preventers (Watts SD-2 dual-check with an atmospheric vent) to be accessible for inspection, maintenance and where water leakage will not cause damage. Reference: Section 608.14, IPC 2012.
3. Provide cleanouts for all horizontal drains (e.g. the branch with lavatories and drinking fountain and the branch from the floor drain, FD-2, and the sink, S-1); the cleanouts shall be sized per Section 708.7, IPC 2012. Reference: Section 708.3.1, IPC 2012.
4. Provide an additional cleanout for each 40-foot section of drains having a change of direction greater than 45 degrees. Reference: Section 708.3.3, IPC 2012.
5. Provide an air gap discharge for the potable clear water waste from the ice machine and the storage-type water heater. Reference: Section 802.1.3, IPC 2012.
6. Clarify the type of venting that has been used for the electric water cooler as shown on sheet P101-1. Reference: Section 901.2.1, IPC 2012.
7. Verify that all of the vents rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012.
8. Provide protection of the trap seals for floor drain FD-2. Reference: Section 1002.4, IPC 2012.
02/19/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide the mechanical energy code compliance certification for the installation of the new mechanical equipment. Reference: Section C303.1, International Energy Conservation Code 2012.
2. Condensate drains may not terminate over a roof drain unless the roof drain terminates at or above grade in an area capable of absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson.
3. Provide information on the sequence of operation for the restroom exhaust fans to show that all of the air supplied to the restrooms will be exhausted with no more than 10% exhausted air being recirculated. Reference: Section 403.2.1 (4), IMC 2012
4. Provide calculations demonstrating adequate ventilation using the current code. Reference: Section 403.2, IMC 2012.
5. The occupant load used to calculate the required ventilation is not necessarily the same as the occupant load used for calculating exiting requirements. The occupant load used for calculating the minimum required ventilation is to be based on Table 403.3, IMC 2012 (e.g. telephone/data entry has an occupancy rate of 60 people pre 1,000 square feet) or an approved engineering analysis of the specific occupancy type with supporting statistical data. Reference: Section 403.3, IMC 2012.