Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T13CM00547
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/19/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Sheets A1.01 and A2.01 not included in this submittal as indicated by the Revision #1 Sheet List provided. 2. Don't see scuppers added on Sheet A3.03 T13CM00547 STRUCTURAL REVIEW REVISIONS FROM 4-30-2013 3. SHEET S-3.04; ADD SHEARWALL DOOR OPENINGS: VERIFY THAT UPDATED CALCULATIONS DUE TO THE OPENINGS DID NOT REQUIRE A CHANGE IN THE SHEARWALL DESIGN AS INDICATED ON THE DRAWINGS. 4. SHEET S-4.01; ADD DETAILS: NO REVISIONS ON THIS SHEET INDICATED REVISION 6. CLARIFY ANY CHANGES. 5. SHEET S-4.02; ADD DETAILS: IN THE REVISIONS BOX, THERE ARE TWO REVISION 6'S NOTED. CLARIFY ANY CHANGES (DETAIL 134 HAS THE ONLY REVISION 6 INDICATED). 6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. END OFN REVIEW |
| 06/25/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The revised sheet M-2.12 shows keynote 5 associated with the fan coil unit FC-1202; what is keynote 5 and where is keynote 4? 2. The relocation of the washer/dryer unit in the 5 bedroom /5 bath apartments will directly affect the dryer exhaust ducts and the access points for the dryer exhaust booster fans. Provide an updated drawing for the enlarged mechanical plans (i.e. M-3.07). |
| 06/25/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the proposed revisions on sheet P2.01; revision delta 7 is indicated in the title block but does not appear on the drawing. The submitted drawing appears to be unchanged from the latest drawing on file, revision delta 6. In addition, the water meter set is still shown in the pump room; Tucson Water has indicated that there is insufficient space for the meter set in that location. 2. Revise the drain for the Jacuzzi located near column D-1.5 on the third floor; it is shown connecting to a roof drain leader. Reference: Section 1104.2, IPC 2012. 3. Verify the cumulative areas being accommodated by the horizontal storm drainage piping on the third floor. |
| 06/26/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/27/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | Just a reminder to comply with 2012 IFC 914.3.1.2 Water Supply for Fire Pump |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/11/2013 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |