Permit Number: T13CM00547
Parcel: 11504520A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13CM00547
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/26/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEET 5.11
1. Detail 4 (Unit 813) is not the same floor plan as Unit 813 shown on sheet A208. Please reconcile.
2. Detail 3 (Unit 604):
a. Showers must be roll in, no curb.
b. On Sheet A206, Unit 604 has no type "A" identification. Please reconcile.
3. Detail 2 (Unit 207) is not the same as Unit 207 as shown on Sheet A202.
4. Detail 1 (Unit 402) is not the same as Unit 402 as shown on Sheet A204.
5. Sheet A405 identifies Unit 605 as the Type "A" unit while detail 3/A5.11 references unit 604??
5. Sheet 7.04 has not been removed from the set. Please do so.
END OF REVIEW
04/29/2013 MARTIN BROWN FIRE REVIEW Approved
04/29/2013 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: The HUB
T13CM00547
Building Plan (3rd Review)

TRANSMITTAL DATE: April 29, 2013


1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning has reviewed the building plans they appear to match the development package.

3. Due to the amount of comments from other PDSD review agencies Zoning will not stamp and approve the building plans at this time.

4. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
05/09/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/10/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
05/13/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved