Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T13CM00509
Parcel: 12511191E

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T13CM00509
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/25/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/26/2013 KEN BROUILLETTE FIRE REVIEW Approved
04/01/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/01/2013 ROBERT SHERRY WATER REVIEW Approved
04/01/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Specifications for a programmable thermostat were not found in this submittal. [Original comment: Provide a programmable thermostat for each air handler that complies with the requirements of Sections R403.1.1 and R403.1.2, IECC 2012.]
2. Provide the air leakage rating for the specified air handler. [Original comment: Show the complete specifications for each heat pump system, including the SEER for each split system, any supplemental heaters, and the air leakage rating of the air handler (ASHRAE Standard 193). Reference: Sections R103.2 and R403.2.2.1, IECC 2012.]
3. Show the size, routing, and termination of the secondary condensate drains for the air handlers. [Original comment: Show the size, routing, and termination of the primary and secondary condensate drains for the air handlers. Reference: Sections 307.2, IMC 2012 as amended by the City of Tucson.]
4. The ventilation for the dwelling units shall be in accordance with the requirements of the 2012 IMC, not the 2000 or 2009 IMC editions. [Original comment: Show how ventilation is to be provided for each apartment. Reference: Section 401.2, IMC 2012.]
04/08/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/11/2013 CPIERCE1 REJECT SHELF Completed