Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T13CM00496
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM00496
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/28/2013 STEVE SHIELDS ZONING REVIEW Approved
01/28/2013 LAITH ALSHAMI ENGINEERING REVIEW Approved
01/28/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/28/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET CS; CODE INFORMATION (APPLICABLE CODES): REVISE THE CODES LISTED TO: 2012 IBC, IMC, IFC, ENERGY CONSERVATION, IPC, AND UPC. 2011 NEC. 2009 ICC/ANSI. VERIFY THAT THE REQUIREMENTS OF THESE CODES HAVE BEEN MET.
2. SHEET A1.1; KEY NOTES: NOTE 10 WAS NOT LOCATED ON THE PLAN. VERIFY.
3. SHEET A1.2; DETAILS 1 AND 2: THE DETAILS REFERENCE 3/A6 FOR THE METAL TIN CEILING. IS THAT CORRECT? VERIFY.
4. SHEET A2; SHELF ELEVATIONS: PROVIDE DETAILS ON THE DRAWINGS (NOT ON 8 1/2 X 11) FOR THE CONNECTION OF THE SHELVES TO THE FLOOR.
5. SHEET A5; KEY NOTES: NOTE 5 REFERENCES DETAIL 3/A6. IS THAT CORRECT? VERIFY.
6. SHEET A5; KEY NOTES: NOTE 2 REFERENCES DETAIL 2/A6.2. REVISE (NO SHEET A6.2).
7. SHEET A13; ELEVATION 2: PROVIDE A DIMENSION TO THE PAPER DISPENSER PER ICC/ANSI A117.1, FIGURE 604.9.2.
8. SHEET S1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE GENERAL NOTES.
9. SHEETS S2, S2.1, S2.2, S3, S4, AND S6: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE SHEET NOTES, AND DETAIL/SECTION VERBIAGE.
10. SHEET S6: ARE THE NEW MECHANICAL UNIT WEIGHTS SIMILAR TO THE PREVIOUS WEIGHTS? VERIFY.
11. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
01/28/2013 ERIC NEWCOMB ADA REVIEW Passed
01/29/2013 KEN BROUILLETTE FIRE REVIEW Denied PLANS NEED TO BE DESIGNED TO THE 2012 INTERNATIONAL CODES
01/30/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Terminate condensate drains in accordance with Section 307.2.1, IMC 2012, as amended by the City of Tucson.
2. Provide calculations demonstrating adequate ventilation. Reference: Section 403.2, IMC 2012, as amended by the City of Tucson.
3. Revise the font size used on the drawings (e.g. M3) to a minimum of 3/32-inch. Reference: Section 107.2.1, IBC 2012.
01/30/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide tempered water for the lavatories using approved devices conforming to ASSE 1070. Reference: Section 416.5, IPC 2012.
01/30/2013 ROBERT SHERRY WATER REVIEW Approved
01/30/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
02/08/2013 GERRY KOZIOL WWM REVIEW Approved