Permit Number: T13CM00436
Parcel: 12801005H

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13CM00436
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/06/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13cm00436

1. Circuits L-39 and 40 used for power shown as spares in Panel L.
2. The existing Panels H and L not shown clearly for location, new Lighting Contactor appears to be on same wall, how will required clearance be obtained ?
3. Sheet E4.0, all text must be minimum 3/32'',as required
by Submittal Requirements.

Ray T Majuta
Elect Plan Review
PDSD, City of Tucson
2/06/2013